Control Options for Industrial Direct Fired Heaters
 

Clogged filter switch with light:
senses air pressure drop across the filter, and is mounted in unit. When the filter becomes dirty, the switch activates a remote control panel light, indicating a required filter change.
 
Convenience-unit outlet, power by others:
provided with a 20-amp, 115-volt, GFCI outlet receptacle for field wiring to customer's 115/1/60 power supply.
 
Dual-range selector dial, 90°-140°F, 401M:
allows for two, separate discharge temperature setpoints for spray and dry modes in both paint booth applications.
 
Electronic time clock
A clock which cycles the unit on and off, or changes from day to night operation, at selected times of the day.
 
Fire stat, discharge:
250°F rated high-limit control mounted in the blower discharge. If the discharge temperature exceeds the control's settings, the unit shuts down. Requires manual reset of control.
 
Flame-failure unit shutdown:
relay interlocked with flame-safety relay. When burner fails to light within 30 seconds, the relay energizes, opening the blower-starter circuit and shuts down the unit.
 
High gas-pressure regulator:
required on all applications where the unit's inlet gas pressure exceeds 2 psi.
 
High gas-pressure switch:
stops unit operation when unit's inlet gas pressure exceeds setpoint. Standard on all FM manifolds over 2,500 MBTU and on FIA (IRI) manifolds over 150 MBTU.
 
High temperature option:
adapts unit with special construction and controls to high temperature paint-booth and industrial-process heating applications.
 
Low fire start:
allows burner circuit, with an electrical interlock, to energize when modulation control is in low fire. This is accomplished with a relay circuit on Maxitrol Systems.
 
Low gas-pressure switch:
stops unit's operation when inlet gas pressure goes below setpoint. Standard on FM manifolds over 2,500 MBTU and on FIA (IRI) manifolds over 150 MBTU.
 
Low-temperature blower shutdown with bypass timer:
shuts blower off if discharge temperature drops below 40°F for longer than five minutes.
 
Operating lights on remote panel:
Up to five labeled pilot lights mounted on a remote control panel face, indicating unit's primary functions.
  1. clear: blower run light
  2. clear: burner on light
  3. amber: low-temperature failure light
  4. red: flame failure shutdown light
  5. amber: clogged filter light

 
Pre-purge timer:
allows unit's blower to run for one minute, purging any gas residue in the unit, before the burner circuit can energize.
 
Pressure gauge, 0-35":
monitors supply pressure to unit, or to burner on gas manifold. Reads low gas pressures between 0 and 35".
 
Pressure gauge, 0-15#:
monitors supply pressure to unit, or to burner on gas manifold. Reads low gas pressures between 0 and 15#.
 
Proof of closure:
gas manifold supplied with a motorized gas valve and an internal micro switch. The valve must be in a closed position, with micro-switch contact closed, before main burner can energize.
 
Smoke detector and sampling tube:
stops unit's operation when smoke is detected. An ionization smoke detector and sampling tube are shipped loose for field mounting.
 
Variable air volume:
allows unit to adjust to a building's variable exhaust loads automatically. Used with a variable frequency drive, the unit can turndown air volume to 40% of full capacity. Fast-acting dampers maintain proper air velocity across burner. Control interface prevents overfiring at low speeds.