PCU Series Specification

Model:

PCU Series


Description: 

Unit shall be factory assembled pollution control unit capable of significantly reducing smoke, grease, and odor from the exhaust air stream.

Certifications: 

Unit shall be listed ETL listed to UL-710, CAN/ULC-S646, CAN/ULC0S647 and UL Listed to UL-1978/ULC-S662 ( Bolted Door Design )

Construction:

Housing

The PCU housing is to be constructed of 430 SS of polish 2B or better. All metal in contact with the air-stream is to be constructed of 430SS. 1500°F Ceramic based gasket must be in place for all internal seams exposed to airflow. High temperature weatherproofing gasket must be used on all exterior seams.

Base

The base shall be constructed of galvanized steel for improved rigidity. Base shall be structurally reinforced to accommodate the filter assembly.

Pre-Filter Section

The pre filter section shall include 2 inch deep steel washable permanent filters. Filter frames shall be constructed of steel. Disposable Grease Lock filters (optional) placed upstream of the permanent filters shall be provided for improved filtration and longevity of High Efficiency Filters. Filters shall be arranged in a v-bank configuration to increase filter area and reduce static pressure. All filters shall be removable without the use of tools through side access doors with lift and turn latches. Filters are to be cleanable with a water hose and soapy water.

High Efficiency Filter Section

The phase two filters shall consist of 4 inch deep rigid cell extended surface filters. Filter cell sides shall be constructed of metallic frame with downstream mesh for durability. Beverage board filter sides shall not be permitted. Filters shall be arranged in a v-bank configuration to increase filter area and reduce static pressure. All filters shall be removable without the use of tools through side access doors with lift and turn latches. Filters are to be rated MERV15 minimum in accordance with ASHRAE standard 52.2 and have a minimum average arrestance of 98% in accordance with ASHRAE 52.1-1992. High Efficiency module must be installed downstream of pre-filter module.

HEPA Filter Section

The phase two filters shall consist of 4 inch deep rigid cell extended surface filters. Filter cell sides shall be constructed of metallic frame with downstream mesh for durability. Beverage board filter sides shall not be permitted. Filters shall be arranged in a v-bank configuration to increase filter area and reduce static pressure. All filters shall be removable without the use of tools through side access doors with lift and turn latches. Filters are to be rated MERV17 minimum in accordance with ASHRAE standard 52.2. HEPA module must be installed downstream of High Efficiency filter module.

Odor Control Media Section (Optional)

The phase two filters shall consist of 4 inch deep rigid cell extended surface filters. Filter cell sides shall be constructed of metallic frame. Beverage board filter sides shall not be permitted. Filters shall be arranged in a v-bank configuration to increase filter area and reduce static pressure. All filters shall be removable without the use of tools through side access doors with lift and turn latches. High Efficiency module must be installed downstream of pre-filter module.

Advanced Filter Monitoring System (Optional)

The Advanced Filter Monitoring includes a module that provides the necessary precision pressure measurements for accurate monitoring of the complete system. Based on the measurements the AFM will initiate suitable actions via the electric control package in case of a fault. Direct access to the operating conditions are also provided through the use of a HMI (Human Machine Interface), which is conveniently located on the PCU.

CORE Protection Fire System (Optional)

The detection portion of the fire suppression system allows for automatic detection by means of an electric thermal detector located in the intake and outlet of the unit. If the Pollution Control Unit Firestat senses a temperature hotter than its internal setpoint, an electric signal is sent to the CORE Fire System Cabinet. An electric water solenoid is energized allowing the flow of water to the Pollution Control Unit mounted manifold. The CORE fire suppression system is a pre-engineered, pollution control unit fire system that utilizes a water spray system for fast flame knock-down and suppression.

Product: Fan shall be model PCU Series as manufactured by CaptiveAire Systems.