| READ AND SAVE THESE INSTRUCTIONS |
| INSTALLATION, OPERATING INSTRUCTIONS & PARTS MANUAL |
| Centrifugal Upblast Exhaust Fan (Standard & High Pressure Exhaust) |
| Belt Driven for Roof & Wall Mounting |
| Electrical wiring and connections should be done in accordance with local ordnances and the National Electric Code, NFPA70. Be sure the voltage and phase of the power supply and the wire amperage capacity is in accordance with the motor nameplate. For additional safety information refer to AMCA publication 410-96, Recommended Safety Practices for Users and Installers of Industrial and Commercial Fans. |
|
||||||
| Upon receiving unit, check for any damage and report it immediately to the carrier. Also check that all accessory items are accounted for. | ||||||
|
|
||||||
| Installation of this ventilator should only be performed by a qualified professional who has read and understands these instructions and is familiar with proper safety precautions. Improper installation poses serious risk of injury due to electric shock, contact with rotating equipment and other potential hazards. Special considerations resulting from high winds or seismic activity may be required. Consult with a licensed professional engineer for more information if necessary. | ||||||
|
||||||
|
||||||
| WARNING: DISCONNECT POWER BEFORE INSTALLING OR SERVICING. | ||||||
| Caution: Do not raise ventilator by its windband, wheel, motor or bearings use a sling or platform | ||||||
| Roof Mounting | ||||||
|
||||||
| Wall Mounting | ||||||
|
||||||
|
||||||
|
||||||
|
||||||
| Pulley alignment is adjusted by loosening the motor pulley or driven pulley set screws and moving the pulley on the shaft. See Fig. 2. A straight edge should be used when aligning pulleys. |
|
| Fig. 2 |
|
||||||
| Belt tension should be checked after the first 48 hours of fan operation. Do not tension belts by changing the setting of the motor pulley, this will change the fan speed and may damage the motor. To re-tension belts, with the power to the fan motor OFF. Loosen the fasteners that hold the motor to the motor mounting plate. Slide the motor to the left or right to adjust the belt tension. Belt tension should be adjusted to allow 1/64 of deflection per inch of belt span. See Fig. 3. Exercise extreme care when adjusting V-belts as not to misalign pulleys. Any misalignment will cause a sharp reduction in belt life and produce squeaky noises. Overtightening will cause excessive belt and bearing wear as well as noise. Too little tension will cause slippage at startup and uneven wear. Whenever belts are removed or installed, never force belts over pulleys without loosening motor first to relieve belt tension. |
|
| Fig. 3 |
|
|||||||||||
|
The adjustable motor pulley is factory set for the RPM specified.
Speed can be increased by closing or decreased by opening the
adjustable motor sheave. Two groove variable pitch pulleys must be
adjusted an equal number of turns open or closed. Any increase in speed
represents a substantial increase in horsepower required by the unit. Motor
amperage should always be checked to avoid serious damage to the motor when
the speed is varied.
In order to adjust the pulley there is an adjustable sheave on the motor. There are two hex set screws on the pulley. One secures the pulley to the shaft. The other allows the two halves of the pulley to be adjusted closer together or further apart. Be sure when adjusting retighten the set screws on a flat side of the pulley base. Adjusting the halves closer together increases the fan speed, further apart slows it down. Double grove pulleys must be turned the same number of turns or the belts will not seat properly in the groves. Always check motor amperage after adjusting pulleys. |
|||||||||||
|
|||||||||||
| WARNING: DO NOT ATTEMPT MAINTENANCE ON THE FAN UNTIL THE ELECTRICAL SUPPLY HAS BEEN COMPLETELY DISCONNECTED. | |||||||||||
|
|||||||||||
|
|||||||||||
|
|||||||||||
|
||||||
|
||||||
|
||